Unit of Measure

Technical Data

Interface

N/A Analog 4 – 20 mA

Operating Voltage

N/A DC 24 V (DC 12 – 30 V)

Temperature Measuring Range

N/A -40 to +60 °C (-40 to +140 °F) ±1 K tolerance
Humidity Measuring Range1 N/A 0 to 100 % RH ±4 % RH tolerance

Channels

N/A 2 x output

Specifications

Mounting

N/A Clip for 35 mm DIN rail, EN 60715 and screw fixing M5

Dimensions

N/A 5.5 x 1.6 x 1.5” (140 x 40 x 38 mm)

Agency Approvals

N/A VDE and UL File No. E500143 (acc. to IEC 61010-1/DIN EN 61010-1)

Weight

N/A Approx. 50 g

Protection Type

N/A IP20

Protection Class

N/A III (SELV)

Max. Reaction Time

N/A 3 min.

Load Resistance (External)

N/A <=500 O

Max. Power Consumption

N/A 1.8 W (typically 0.4 W)

Connection

N/A M12 round plug connector, IEC 61076-2-101, 4-pin, A-coded, shielded

Electrical Protection

N/A Reverse-polarity, short circuit, overvoltage protection

Casing

N/A plastic according to UL94 V-0, light grey

Fitting Position

N/A Vertical (connection on top)

Operating/Storage Temperature

N/A -40 to +70 °C (-40 to +158 °F) / -40 to +85 °C (-40 to +185 °F)

Operating / Storage humidity

N/A max. 90 % RH (non-condensing)
  • 1 Tolerance within 20 to 80 % RH (please request diagram for tolerances outside this range)