Unit of Measure

Specifications

Voltage

N/A DC 12-48 V (min. DC 10 V, max. DC 60 V)

Setting Range

N/A -20 to +60 °C

Agency Approvals

N/A VDE submitted

Technical Data

Contact Type

N/A SPDT / change-over contact (relay)

Service LIfe

N/A >100,000 cycles (at 10 mW)

Max. Switching Capacity (Relay Output)

N/A 0.5 A at DC 48 V

Operating/Storage Humidity

N/A Max. 95 %RH (non-condensing)
Connection1 N/A 5-pole terminal, clamping torque 0.5 Nm max.: solid/stranded wire - AWG 14 max. (2.5 mm2)

Housing

N/A Plastic, UL 94V-0, light grey

Mounting

N/A Clip for 35 mm DIN rail, EN 60715

Mounting Position

N/A Vertical

Dimensions

N/A 2.54 x 1.65 x 1.5" (64.5 x 42 x 38 mm)

Weight

N/A Approx. 2.5 oz. (70 g)

Protection Type

N/A IP20

Reaction Time

N/A Approx. 5 sec.

Optical Indicator

N/A LED

Switching Difference (temperature)

N/A 7 °F (4 K) ± 1.8 °F (1 K) tolerance at +68 °F (+20 °C)

Switching Load

N/A DC 10 mW (at 0.1 V, 100 mA or 1 mA, 10 V)

Operating/Storage Temperature

N/A -40 to +185 °F (-40 to +85 °C)

Sensor Element

N/A NTC
  • 1 When connecting with stranded wires, wire end ferrules must be used.